Model | 5MWh-2h | 5MWh-4h |
---|---|---|
Duration of Charging and Discharging | 2h | 4h |
Cell type | 315Ah LFP | 315Ah LFP |
Cell energy | 1008Wh | 1008Wh |
Model | 5MWh-2h | 5MWh-4h |
---|---|---|
Configuration | 12P416S | 12P416S |
System voltage range | 1040-1500V | 1040-1500V |
Rated power | 2515 kW | 1257 kW |
Installed energy | 5031 kWh | 5031 kWh |
Round-trip efficiency | 94% | 95% |
Dimensions (L*W*H) | 20 feet (6058 mm*2438 mm*2896 mm) | 20 feet (6058 mm*2438 mm*2896 mm) |
Weight | ≤44000kg | ≤44000kg |
DOD | 0%-100% | 0%-100% |
Type of cooling | Liquid-cooling | Liquid-cooling |
Communication protocol | Modbus TCP, CAN 2.0, IEC 104 | Modbus TCP, CAN 2.0, IEC 104 |
Degree of protection | IP55 | IP55 |
Fire protection | Pack-level fire detection + perfluorohexanone fire extinguishing system + standard explosion-proof ventilation system + back-up fire water system (optional) | Pack-level fire detection + perfluorohexanone fire extinguishing system + standard explosion-proof ventilation system + back-up fire water system (optional) |
Operating temperature range | -30~50℃ | -30~50℃ |
Operating relative humidity | 0%~95% (non-condensing) | 0%~95% (non-condensing) |
Maximum working altitude | 2000m | 2000m |
Model | 5MWh-2h | 5MWh-4h |
---|---|---|
Cell-level certification | UL 9540A, UL1973, IEC62619 | UL 9540A, UL1973, IEC62619 |
Rack-level certification | UL 9540A, UL1973, IEC62477 | UL 9540A, UL1973, IEC62477 |
System-level certification | NFPA 855, NFPA 68/69, IEC62933, UL 9540 | NFPA 855, NFPA 68/69, IEC62933, UL 9540 |
Model | 5MWh-2h | 5MWh-4h |
---|---|---|
Peak-valley arbitrage | √ | √ |
Demand control | √ | √ |
Frequency modulation at power-side and grid-side | √ | √ |
Active/reactive power control | √ | √ |
Black start | √ | √ |